<?xml version="1.0" encoding="UTF-8"?>
<rss version="2.0"
	xmlns:content="http://purl.org/rss/1.0/modules/content/"
	xmlns:wfw="http://wellformedweb.org/CommentAPI/"
	xmlns:dc="http://purl.org/dc/elements/1.1/"
	xmlns:atom="http://www.w3.org/2005/Atom"
	xmlns:sy="http://purl.org/rss/1.0/modules/syndication/"
	xmlns:slash="http://purl.org/rss/1.0/modules/slash/"
	>

<channel>
	<title>Новости рынка ЦОД, обзор инженерных решений Дата-Центров &#187; АУГПТ</title>
	<atom:link href="http://telecombloger.ru/category/data-centers/sistemy-protivopozharnoj-zashhity/feed" rel="self" type="application/rss+xml" />
	<link>http://telecombloger.ru</link>
	<description>Вся правда о телекоммуникациях</description>
	<lastBuildDate>Thu, 02 Feb 2012 18:17:48 +0000</lastBuildDate>
	<generator>http://wordpress.org/?v=2.9.2</generator>
	<language>en</language>
	<sy:updatePeriod>hourly</sy:updatePeriod>
	<sy:updateFrequency>1</sy:updateFrequency>
			<item>
		<title>Доклад по 3M Novec 1230 на DataCenterDynamics в Санкт-Петербурге</title>
		<link>http://telecombloger.ru/8663</link>
		<comments>http://telecombloger.ru/8663#comments</comments>
		<pubDate>Wed, 15 Jun 2011 09:21:04 +0000</pubDate>
		<dc:creator>author</dc:creator>
				<category><![CDATA[АУГПТ]]></category>
		<category><![CDATA[Инфраструктура ЦОД]]></category>
		<category><![CDATA[Новости]]></category>
		<category><![CDATA[3M]]></category>
		<category><![CDATA[DatacenterDynamics]]></category>
		<category><![CDATA[DataSpace]]></category>
		<category><![CDATA[Novec]]></category>
		<category><![CDATA[SF6]]></category>
		<category><![CDATA[Азот]]></category>
		<category><![CDATA[Аргон]]></category>
		<category><![CDATA[Инерген]]></category>
		<category><![CDATA[Хладон]]></category>

		<guid isPermaLink="false">http://telecombloger.ru/?p=8663</guid>
		<description><![CDATA[На прошлой неделе я принял участие в конференции DataCenterDynamics, проходящей в Санкт-Петербурге, к сожалению, побывать на всех докладах не удалось, так как программа была рассчитана на две параллельных  сессии,  но наиболее интересные презентации мне посетить удалось, о некоторых из них я Вам и расскажу.
В прошлом году публикация материала “Огнетушащий газ нового поколения Novec™ [...]]]></description>
			<content:encoded><![CDATA[<p><a href="http://telecombloger.ru/8663/imag0119" rel="attachment wp-att-8681"><img src="http://telecombloger.ru/wp-content/uploads/2011/06/IMAG0119-1024x613.jpg" alt="" title="конференция DataCenterDynamics, проходящая в Санкт-Петербурге" width="400" height="239" class="aligncenter size-large wp-image-8681" align="left"/></a>На прошлой неделе я принял участие в конференции DataCenterDynamics, проходящей в Санкт-Петербурге, к сожалению, побывать на всех докладах не удалось, так как программа была рассчитана на две параллельных  сессии,  но наиболее интересные презентации мне посетить удалось, о некоторых из них я Вам и расскажу.</p>
<p>В прошлом году публикация материала “<a href="http://telecombloger.ru/1868" target="_BLANK">Огнетушащий газ нового поколения Novec™ 1230 (Новак™ 1230)</a>” вызвал достаточно бурную реакцию, были заданы ряд вопросов, на которые я получил ответы в ходе презентации и в частном разговоре с Антоном Анненковым из Пожтехники.<br />
<span id="more-8663"></span><br />
Начнем с того, что на основе свода правил МЧС России СП5.13130.2009: “Помещения связаных процессоров (серверов), архивов магнитных и бумажных носителей, графопостроителей, печати информации на бумажных носителях (принтерные) свыше  24  кв.м. подлежат защите автоматическими установками пожаротушения” (Приложения А).</p>
<h3>Виды газового пожаротушения</h3>
<ul>
<li> <strong>Сжатые газы</strong><em>CO2, Азот, Аргон, Инерген </em>
<ul>
<li> Подавления огня за счет разбавления кислорода воздуха</li>
<li> Высокие рабочие концентрации (35-40%)</li>
<li> Исключение присутствия персонала (концентрации выше или близки к смертельным )</li>
<li> Инерционность системы (более 60 сек.)</li>
<li> Значительные габариты установки</li>
<li> Специальные требования к помещениям (сбросные клапаны, блокировки дверей)</li>
<li> <strong>Воздействие на оборудование: </strong> При неисправности сбросных клапанов возможно механическое повреждение оборудования и ограждающих строительных конструкций из-за значительного повышения температуры</li>
<li> <strong>Возгорание: </strong>
<ul>
<li> Задержка пуска для эвакуации персонала 10…30 сек.</li>
<li> Создание рабочей концентрации 60 сек.</li>
<li> Начало тушения после определения возгорания 70… 90 сек.</li>
</ul>
</li>
</ul>
</li>
<li> <strong>Сжиженные газы</strong><em> SF6, Хладоны, CO2</em>
<ul>
<li> Химическое разложение в пламени и подавление горения</li>
<li> Низкая рабочая концентрация (7-10%)</li>
<li> Низкая инерционность (10 сек.)</li>
<li> Установки компактны</li>
<li> Конденсация влаги в помещении и угроза повреждения оборудования</li>
<li> Экологические ограничения</li>
<li> <strong>Воздействие на оборудование: </strong> Падение температуры в помещении на 10-15 градусов C при выпуске хладона, массовая конденсация влаги воздуха, осаждение на оборудование вместе с продуктами горения, повреждение и загрязнение оборудования</li>
<li> <strong>Возгорание: </strong>
<ul>
<li> Задержка пуска для эвакуации персонала 10…30 сек.</li>
<li> Создание рабочей концентрации 10 сек.</li>
<li> Начало тушения после определения возгорания 20… 40 сек.</li>
</ul>
</li>
</ul>
</li>
<li> <strong>Жидкие ГОТВ с газом вытеснителем</strong><em> 3M Novec 1230</em>
<ul>
<li> Физический механизм тушения</li>
<li> Самая низкая огнетушащая концентрация (4,2%)</li>
<li> Быстрота работы системы (отсутствие задержки выпуска)</li>
<li> Безопасность для электроники</li>
<li> Безопасность для персонала (запас в 2,4 раза)</li>
<li> Отсутствие экологических ограничений</li>
<li> <strong>Воздействие на оборудование: </strong> При распылении возможно падение температуры не более чем на 1…2 градуса, что не приводит к конденсации. Попадание на оборудование не вызывает коррозии, образования налета, замыканий</li>
<li> <strong>Возгорание: </strong>
<ul>
<li> Создание рабочей концентрации 10 сек.</li>
<li> Начало тушения после определения возгорания &lt; 10   сек.</li>
</ul>
</li>
</ul>
</li>
</ul>
<h3>Ограничение использования хладонов</h3>
<ul>
<li><strong> Монреальский протокол</strong><br />
Постановление Правительства  РФ от  5 мая 1999 г. №490 <strong>“Об усилении мер государственного регулирования производства и потребления озоноразрушающих веществ в Российской Федерации”</strong><br />
В 2000 г. В России выпуск, экспорт и импорт озоноразрушающих хладонов прекращеню.<br />
В газовом пожаротушении это коснулось хладонов: 13В1, 12В1, 12В2, 11В1, 1211,1301, 2402.</li>
<li><strong> Киотский протокол</strong><br />
Федеральный закон от 4 ноября 2004 г. №128-ФЗ <strong>“О ратификации Киотского протокола к Рамочной конвенции Организации Объединенных Наций об изменении климата”</strong></li>
</ul>
<h3>Огнетушащие и экологические свойства</h3>
<table border="1" cellspacing="0" cellpadding="0">
<tbody>
<tr>
<td width="130" valign="top">Газовое</p>
<p>Огнетушащее</p>
<p>вещество</td>
<td width="104" valign="top">Рабочая</p>
<p>концентрация</td>
<td width="82" valign="top">NOAEL</td>
<td width="106" valign="top">Запас</p>
<p>безопасности</td>
<td width="106" valign="top">Потенциал</p>
<p>Глобального</p>
<p>потепления</td>
<td width="111" valign="top">Время</p>
<p>Существования</p>
<p>В атмосфере</td>
</tr>
<tr>
<td width="130" valign="top">Хладон -1301</td>
<td style="text-align: center;" width="104" valign="top">5 %</td>
<td style="text-align: center;" width="82" valign="top">5 %</td>
<td style="text-align: center;" width="106" valign="top">0 %</td>
<td style="text-align: center;" width="106" valign="top">7140</td>
<td style="text-align: center;" width="111" valign="top">65 лет</td>
</tr>
<tr>
<td width="130" valign="top">Хладон -227еа</td>
<td style="text-align: center;" width="104" valign="top">7,2 %</td>
<td style="text-align: center;" width="82" valign="top">9 %</td>
<td style="text-align: center;" width="106" valign="top">25 %</td>
<td style="text-align: center;" width="106" valign="top">3220</td>
<td style="text-align: center;" width="111" valign="top">29 лет</td>
</tr>
<tr>
<td width="130" valign="top">Хладон -125</td>
<td style="text-align: center;" width="104" valign="top">9,8 %</td>
<td style="text-align: center;" width="82" valign="top">7,5 %</td>
<td style="text-align: center;" width="106" valign="top">-23 %</td>
<td style="text-align: center;" width="106" valign="top">3500</td>
<td style="text-align: center;" width="111" valign="top">34,2 года</td>
</tr>
<tr>
<td width="130" valign="top">Инерген</td>
<td style="text-align: center;" width="104" valign="top">36,5 %</td>
<td style="text-align: center;" width="82" valign="top">43 %</td>
<td style="text-align: center;" width="106" valign="top">18 %</td>
<td style="text-align: center;" width="106" valign="top">-</td>
<td style="text-align: center;" width="111" valign="top">-</td>
</tr>
<tr>
<td width="130" valign="top">CO2</td>
<td style="text-align: center;" width="104" valign="top">34,9 %</td>
<td style="text-align: center;" width="82" valign="top">&lt; 5 %</td>
<td style="text-align: center;" width="106" valign="top">-85 %</td>
<td style="text-align: center;" width="106" valign="top">1</td>
<td style="text-align: center;" width="111" valign="top">-</td>
</tr>
<tr>
<td width="130" valign="top">Novec™ 1230</td>
<td style="text-align: center;" width="104" valign="top">4,2 %</td>
<td style="text-align: center;" width="82" valign="top">10 %</td>
<td style="text-align: center;" width="106" valign="top">138 %</td>
<td style="text-align: center;" width="106" valign="top">1</td>
<td style="text-align: center;" width="111" valign="top">3-5 дней</td>
</tr>
</tbody>
</table>
<h3>Количество модулей ГПТ на объем 3500 м. куб.</h3>
<table border="1" cellspacing="0" cellpadding="0">
<tbody>
<tr>
<td style="text-align: center;" width="165" valign="top"><strong>Инерген</strong></td>
<td style="text-align: center;" width="163" valign="top"><strong>Хладон -125хп</strong></td>
<td style="text-align: center;" width="163" valign="top"><strong>Хладон -227Еа</strong></td>
<td style="text-align: center;" width="148" valign="top"><strong>3М Novec™ 1230</strong></td>
</tr>
<tr>
<td width="165" valign="top">
<p style="text-align: center;">126(63) шт.</p>
</td>
<td width="163" valign="top">
<p style="text-align: center;">46(23) шт.</p>
</td>
<td width="163" valign="top">
<p style="text-align: center;">36(18) шт.</p>
</td>
<td width="148" valign="top">
<p style="text-align: center;">28(14) шт.</p>
</td>
</tr>
</tbody>
</table>
<h3>Идеальный огнетушащий газ</h3>
<p>По мнению специалистов компании Пожтехника и 3М идеальный огнетушащий газ должен обладать следующими качествами:</p>
<ul>
<li>Чистым</li>
<li>Быстродействующим/Эффективным</li>
<li>Доступным</li>
<li>Безлопастным  для окружающей среды</li>
<li> Безлопастным  для  оборудования</li>
<li> Безлопастным  для людей</li>
<li>Общепризнанным, имеющим международный сертификат</li>
</ul>
<h3>Реализация АГП на базе ГОТВ в ЦОД РФ</h3>
<p><UL><br />
<LI> Проекты в работе:<br />
<OL TYPE="1" START="1"><br />
<LI> ЦОД DataSpace Partners (Москва), площадь более – 4000 кв.м. </LI><br />
</OL></LI><br />
<LI> Реализованные проекты:<br />
<OL TYPE="1" START="1"><br />
<LI> ЦОД ОАО МТС в Новосибирске, площадь более – 750 кв.м. </LI><br />
<LI> ЦТОС ОАО МегаФон в г. Дмитров Московская область, площадь более – 1000 кв.м. </LI></p>
<p></OL></LI></UL></p>
<h3>Инсталляции</h3>
<p>По заявления специалиста по технологиям электронной промышленности 3М  Константина Буланова в России уже более 500 объектов, на которых применяют 3M Novec 1230. Выбор в пользу 3M Novec 1230 сделали такие компании как МегаФон, МТС, Газпром, Банк России, РЖД, СберБанк и многие другие.</p>
]]></content:encoded>
			<wfw:commentRss>http://telecombloger.ru/8663/feed</wfw:commentRss>
		<slash:comments>7</slash:comments>
		</item>
		<item>
		<title>Огнетушащий газ нового поколения Novec™ 1230 (Новак™ 1230)</title>
		<link>http://telecombloger.ru/1868</link>
		<comments>http://telecombloger.ru/1868#comments</comments>
		<pubDate>Tue, 09 Feb 2010 07:54:02 +0000</pubDate>
		<dc:creator>author</dc:creator>
				<category><![CDATA[АУГПТ]]></category>
		<category><![CDATA[Инфраструктура ЦОД]]></category>
		<category><![CDATA[Новости]]></category>
		<category><![CDATA[Novec]]></category>

		<guid isPermaLink="false">http://telecombloger.ru/?p=1868</guid>
		<description><![CDATA[Novec™ 1230 – последняя разработка на рынке газовых огнетушащих веществ (ГОТВ). Газовое огнетушащее вещество предназначено для тушения пожара, включая пожар горючих жидкостей, газов и компонентов электрооборудования. Обратите внимание на последний пункт: тушение электрооборудования. Газы не проводят электричество и потому установка газового пожаротушения (УГТВ) тушит электрооборудования без ущерба, в отличие от установки водяного, пенного и порошкового [...]]]></description>
			<content:encoded><![CDATA[<p><img src="http://telecombloger.ru/wp-content/uploads/2010/02/contactcleaner-225x300.jpg" alt="Novec™ 1230" title="Novec™ 1230" width="225" height="300" class="alignnone size-medium wp-image-1869" />Novec™ 1230 – последняя разработка на рынке газовых огнетушащих веществ (ГОТВ). Газовое огнетушащее вещество предназначено для тушения пожара, включая пожар горючих жидкостей, газов и компонентов электрооборудования. Обратите внимание на последний пункт: тушение электрооборудования. Газы не проводят электричество и потому установка газового пожаротушения (УГТВ) тушит электрооборудования без ущерба, в отличие от установки водяного, пенного и порошкового пожаротушения.<br />
<span id="more-1868"></span></p>
<p>Novec™ 1230 – первый «чистый» газ для огнетушения. Он безопасен для человека и окружающей среды.</p>
<p>Отслужив человечеству более полувека, установки с применением Хладонов постепенно выходят из употребления, так как хладоны отрицательно влияют на состояние биосферы планеты, а некоторые запрещены к использованию как особо вредные вещества.</p>
<p>Установки с углекислым газом (СО2) требуют особых условий транспортировки, монтажа и эксплуатации. И углекислый газ в больших количествах опасен для жизни, поэтому может применяться только там, где исключено присутствие человека во время тушения пожара.</p>
<p>Инерген более безпасен для человека (жизнедеятельность при его использовании возможна в течение нескольких минут), но при его использовании вы имеете дело с баллонами, давление в которых целых 300 бар. На практике это приводит к целому комплексу эксплуатационных проблем.</p>
<p>Установки газового пожаротушения, описанные выше, работают как антибиотик, по принципу: одно лечит, другое калечит. Они гасят пожар ценой ущерба человеку и природе. Кроме того, они неудобны в эксплуатации.</p>
<p>Поэтому Novec™ 1230 &#8211; наиболее оптимальный выбор для установок газового пожаротушения: он безопасен для человека и окружающей среды, его легко транспортировать без использования специальной техники и оборудования, установки с его использованием не занимают много места.</p>
<p>Novec™ 1230: будущее пожаротушения</p>
<p>В связи с усилением мер по защите окружающей среды и, принимая во внимание стремление заказчика сократить расходы по содержанию систем безопасности, конкурентоспособное ГОТВ должно отвечать следующим требованиям:</p>
<p>- не наносить вред человеку,</p>
<p>- не воздействовать на окружающую среду,</p>
<p>- занимать минимум места на защищаемом объекте,</p>
<p>- быть удобным в эксплуатации,</p>
<p>- эффективно тушить пожар.</p>
<p>Корпорация 3М разработала инновационное ГОТВ Novec™ 1230, учитывая все эти требования.</p>
<p><strong>Достоинства Novec™ 1230:</strong></p>
<p><strong>Безвредность для человека</strong><br />
Номинальная (рабочая) концентрация Novec™ 1230 составляет лишь треть его максимальной безопасной концентрации (сравните 4,2 % и 10%). Он практически не снижает содержание кислорода в помещении. Поэтому Novec™ 1230 не наносит вреда органам зрения и дыхания человека.</p>
<p><strong>Безопасность для окружающей среды</strong><br />
Novec™ 1230 не содержит брома и хлора. Молекулы Novec™ 1230 распадаются под действием солнечного излучения в течение пяти дней. Таким образом, он не оказывает каких-либо воздействий на изменение климата нашей планеты.</p>
<p><strong>Компактность системы пожаротушения</strong><br />
УГПТ с применением Novec™ 1230 требует минимум пространства для хранения (см. также раздел «Стоимость системы»).</p>
<p><strong>Удобство эксплуатации системы пожаротушения</strong><br />
Novec™ 1230 без проблем перевозится в виде жидкости: без давления, без маркировки «опасный груз». Заправка баллонов возможна на месте. В баллонах Novec™ 1230 храниться под давлением в 25 бар. Так как давление паров в баллоне незначительно, нет необходимости в сбросных вентиляционных отверстиях, применяемых в целях безопасности в системах с высоким давлением.</p>
<p><strong>Эффективность при тушении</strong><br />
Хотя Novec™ 1230 по внешнему виду напоминает жидкость, он поглощает тепло гораздо лучше воды, так как у него слабые молекулярные связями. Например пожар класса А (горение твердых веществ) система с применением Novec™ 1230 тушит в течение 10 секунд. Система так же предназначена для тушения пожаров класса B.</p>
<p><strong>Безопасность для электроники</strong><br />
Газы не проводят электричество и потому установка газового пожаротушения с применением Novec 1230 тушит электрооборудования без ущерба!</p>
<p>Установки газового пожаротушения с применением газового огнетушащего вещества Novec™ 1230 сертифицированы на территории России. УГПТ с применением ГОТВ Novec™ 1230 соответствует нормам пожарной безопасности РФ. Для огнетушащего вещества Novec™ 1230 получено санитарно-эпидемиологическое заключение.</p>
<p><a href="http://www.novec1230.ru/">источник</a></p>